Performance and Theory of Operations

Chapter 7

7-17

In this example,

R

=

1

because the value of D (6 ms) < 15 ms logic scan time

block-transfer duration (ms) = 6 x 1 or 6 ms

The block-transfer duration shown above does not affect logic scan time.
This transfer of data occurs concurrent with execution of program logic.

Remote I/O

The processor performs block transfers asynchronously to the program
scan. The processor also interrupts the program scan asynchronously to
momentarily access BTW and BTR data files. The processor performs one
remote block transfer per addressed rack and per remote I/O scan.
Figure 7.4 shows timing loops for block transfer from a PLC-5/VME
processor.

Figure 7.4
Transferring Block Data to Local and Remote I/O

Rack 7

Remote I/O
Scan

Remote I/O

Rack 6

Rack 5

One transfer per
I/O scan

One transfer per
I/O scan

One transfer per
I/O scan

BTR or BTW Data

BT

Requests

Q

A

BTR or BTW Data

BT Requests

Q

A

BTR or BTW Data

BT Requests

Q

A

Q = Queue
A = Active

Buffer

Q

A

One transfer per
I/O scan

BTR or BTW Data

The adapter used in the remote I/O scan is the

1771-ASB adapter.

Adapter

Adapter

Adapter

BT Requests

Interrupt from STI or Fault Routine

Logic

Scan

Program Scan