3–3

Uploading 1000e/1200e/1400e Application Files and Alarm History Files

Publication 2711E-6.8 – January 1998

Important:

The application file to be uploaded must be the
Current Application in the PanelView terminal.
For more information, refer to “Selecting an
Application” in Chapter 5, “Configuring
PanelView Terminals,” in your PanelView
1000e, 1200e, and 1400e Operator Terminals
User Manual
(Publication Number 2711E-821).

To prepare the PanelView terminal for a network direct upload:

1. Switch the PanelView terminal to the Configure mode, using the

hardware keyswitch or the Goto Configure Mode button.

2. At the PanelView terminal, press the Transfer Setup button on the

Terminal Configuration screen to display the Transfer Setup
screen.

3. Select the Network tab.

4. To do a DH+ Direct or ControlNet Direct transfer, choose either

Application or Network Direct as the Address Source. The first
time you enter this screen, the default is Application if you have
an application selected; otherwise, RIO Pass-Through or the
Address Source that was previously selected is the default. When
you re-enter the screen, the values that were previously saved
appear.

Application — When you choose Application, all the
configuration parameters are taken from the currently-selected
application file. This is the default setting.

Network Direct —When you choose Network Direct, the
configuration parameters from the application file are
disabled.