3-40 Operator
Interface
7000A-UM151D-EN-P – March 2013
7000 “A” Frame
Fault
Masks
 
 
A number of the faults within the drive may be selectively enabled or 
disabled by you. To view or modify the current fault mask settings, 
use the up/down arrow keys on the SETUP screen to select the 'Fault 
Masks' option and press the [enter] key. 
 
 
A typical screen as shown in Figure 3.50 shows all of the user 
maskable faults. Associated with each fault is the state of the mask. 
If OFF, it means the fault is disabled and will not occur. The normal 
state is ON or enabled. 
 
 
To change the state of the mask, use the [cursor up] or [cursor down] 
keys to select the desired fault and press the [enter] key. Each press 
of the [enter] key will toggle the state of the mask as shown in Figure 
3.51. (If nothing happens, you do not have proper access to the 
drive. Exit to the SETUP screen and refer to the section entitled 
Enter/Modify an Access Level to gain access). 
Figure 3.50 – Fault Screen
Figure 3.51 – Fault Mask OFF
Figures 3.50 and 3.51 show all fault masks regardless of their current 
state. The fault masks can be viewed according to their state by 
pressing the [F7] key on the FAULTS SETUP screen. This will 
display the FAULTS OVERVIEW screen, typical of Figures 3.52 
and 3.53.