Motor compatibility – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control (PanelView 550) User Manual
Page 18
 
1-6
Overview of Drive
7000A-UM151D-EN-P – March 2013
7000 “A” Frame
 
 
Motor Compatibility
The PowerFlex 7000 achieves near sinusoidal current and voltage 
waveforms to the motor, resulting in no significant additional heating 
or insulation stress. Temperature rise in the motor connected to the 
VFD is typically 3 °C (5.4 °F) higher compared to across-the-line 
operation. Voltage waveform has dv/dt of less than 10 volts per 
microsecond. Reflected wave and dv/dt issues often associated with 
VSI (voltage source inverter) drives do not exist with the PowerFlex 
7000. Typical motor waveforms are shown in Figure 1.3. These 
motor friendly waveforms are achieved by utilizing a selective 
harmonic elimination (SHE) pattern in the inverter to eliminate 
major order harmonics, in conjunction with a small output capacitor 
(integral to the drive) to eliminate harmonics at higher speeds. 
Standard motors are compatible without de-rating, even on retrofit 
applications. 
 
 
Motor cable distance is virtually unlimited. This technology is capable 
of controlling motors up to 15 km (9.3 miles) away from the drive. 
 
 
300.00
200.00
100.00
0.00
-100.00
-200.00
-300.00
10.00K
7.50K
5.00K
2.50K
0.00K
-2.50K
-5.00K
-7.50K
-10.00K
100.00
110.00
120.00
130.00
TIME (ms)
140.00
150.00
Arms
Vrms
Figure 1.3 – Motor waveform @ full load, full speed
Motor current
Motor voltage