4-20

Component Definition and Maintenance

7000A-UM151D-EN-P – March 2013

7000 “A” Frame

D.C. Link / Fan / Control Components

Analog Drive
Control Board

Medium Voltage
Barrier (for
access to
Line/Motor
Capacitors)

Low voltage
Control Tub
Retaining
Hardware

AC/DC
Power
Supply

Fan

Inlet Ring

DC Link
Inductor

Grounding
Network/
Filter

Motor Filter
Capacitor

Line Filter
Capacitor

M+ L+ L- M-

Figure 4.16 – DC Link and Fan cabinet

with low voltage control tub shown

Figure 4.17 – DC Link and Fan Cabinet

with low voltage control tub removed

When the door is opened, control components are accessible. Behind the
low voltage swing-out panel is the medium voltage compartment where
the DC link and fan are located.

The D.C. link is mounted on the floor plate of the cabinet above the capacitors.

Power connections are made to the inductor via its flexible leads. There
are four power connection points labeled L+, L-, M+, and M-.

The D.C. link is equipped with thermal protection for the windings.

There is a current sensor on the M+ conductor.

Above the D.C. link is the fan.

The primary elements of the fan are the inlet ring, impeller and motor.

The inlet ring is stationary and must not contact the rotating impeller.

Mounted on top of the cabinet is an air exhaust hood. The exhaust hood
must be installed to prevent foreign objects from entering the drive.