Preventative Maintenance Schedule
 
 
 
 
The preventive maintenance activities on the PF7000 Air-Cooled Drive 
(“A” Frame or “B” Frame) can be broken down into two categories: 
•
Operational Maintenance – can be completed while the drive is 
running. 
•
Annual Maintenance – should be completed during scheduled 
downtime. 
 
 
Refer to the Tools/Parts/Information Requirements at the end of this 
section for a list of documentation and materials needed to properly 
complete the preventive maintenance documents. 
 
 
Operational Maintenance
This process really involves only one task: Changing or Cleaning the 
Air Filters. The PF7000 drives require consistent, unrestricted airflow 
to keep the power devices cool. The air filter is the main source of 
blockage in the air path. 
 
 
The drive will provide an air filter alarm whenever the pressure 
differential across the devices drops to a drive-specific level. Referring 
to the Air Filter Block parameter, this can be anywhere from 7% to 17% 
blocked, depending on the heatsink and device configuration. This may 
seem like a small number, but it takes significant blockage to begin to 
lower the voltage from the pressure sensor. The percentage is a measure 
of voltage drop, and should not be viewed as a percentage of the 
opening that is covered. They are not related linearly. 
Once you receive an Air Filter Warning, you should immediately
make plans to change or clean the filter. You should still have days 
or weeks until the drive reaches an Air Filter Fault, but this is 
dependent on site-specific particle conditions. 
 
 
This can be done while the drive is running. Refer to User Manual, 
Chapter 4 – Component Definition and Maintenance for a detailed 
description of the process. 
Preventive Maintenance 
Check List