4-52

Component Definition and Maintenance

7000A-UM151D-EN-P – March 2013

7000 “A” Frame



LED D1 and display U6 indicate the status of the board. The following
table illustrates the possible states for D1.

LED Status

Description

Solid Green

Normal Operation

Solid Red

Board Failure

Alternate Flashing of Red and
Green

No Communication Available to ACB board
(Normal during boot-up or unprogrammed)



Status of U6 Display

Display

Description

Explanation

No valid address found

– More than 6 XIO cards on network
– XIO cable failure
– XIO card failure
– ACB failure

0

Card in “Master” mode

– Rockwell Use Only
– Remove connection to J3 and recycle power

1 – 6

Valid address

– Normal

Decimal point ON

Indicates network activity

– Normal

Decimal point OFF

No activity on the network

– Normal at Power on, during firmware

download and with unprogrammed drive