LED D1 and display U6 indicate the status of the board. The following
table illustrates the possible states for D1.
LED Status
Description
Solid Green
Normal Operation
Solid Red
Board Failure
Alternate Flashing of Red and
Green
No Communication Available to ACB board
(Normal during boot-up or unprogrammed)
Status of U6 Display
Display
Description
Explanation
—
No valid address found
– More than 6 XIO cards on network
– XIO cable failure
– XIO card failure
– ACB failure
0
Card in “Master” mode
– Rockwell Use Only
– Remove connection to J3 and recycle power
1 – 6
Valid address
– Normal
Decimal point ON
Indicates network activity
– Normal
Decimal point OFF
No activity on the network
– Normal at Power on, during firmware
download and with unprogrammed drive