D.c. link / fan / control components (cont.) – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control (PanelView 550) User Manual
Page 150
 
 
 
4-24 
Component Definition and Maintenance
7000A-UM151D-EN-P – March 2013
7000 “A” Frame
 
 
 
2. Follow appropriate safety steps to isolate the equipment from medium
voltage.
 
3. Verify that there is no voltage present on the capacitor by using a hot 
stick or any other appropriate voltage-measuring device.
 
4. Perform visual inspection to ensure there is no oil leak or bulge in any 
of the capacitors.
5. Using a DMM measure the capacitance across each phase-to-neutral
of capacitors without removing any connections. If the difference 
between the highest and the lowest readings is below 15% then all 
capacitors are in good condition. 
 
 
6. If the difference between the highest and the lowest readings is off by
15% or more, then you might have a bad capacitor.
 
7. Before disconnecting the capacitors, note the location of all the cables 
and mark them accordingly.
 
8. Disconnect power cables/bus bars from the capacitor terminals on all 
four bushings and isolate them from the capacitor. (Refer to “Filter 
Capacitor Replacement” guidelines in the Classic User Manual - 
Component Definition and Maintenance chapter (chapter 6) for using 
proper torque when reconnecting the capacitors) 
 
 
Second
Method
1. Ensure there is no power to the equipment before testing the
capacitor.
A T T E N T I O N
A T T E N T I O N
To prevent electrical shock ensure the main 
power has been disconnected before working on 
the capacitor. Verify that all circuits are voltage 
free using a hot stick or appropriate voltage-
measuring device. Failure to do so may result in 
injury or death. 
D.C. Link / Fan / Control 
Components (cont.)