D.c. link / fan / control components (cont.) – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control (PanelView 550) User Manual

Page 150

Advertising
background image



4-24

Component Definition and Maintenance

7000A-UM151D-EN-P – March 2013

7000 “A” Frame



2. Follow appropriate safety steps to isolate the equipment from medium

voltage.


3. Verify that there is no voltage present on the capacitor by using a hot

stick or any other appropriate voltage-measuring device.


4. Perform visual inspection to ensure there is no oil leak or bulge in any

of the capacitors.

5. Using a DMM measure the capacitance across each phase-to-neutral

of capacitors without removing any connections. If the difference
between the highest and the lowest readings is below 15% then all
capacitors are in good condition.


6. If the difference between the highest and the lowest readings is off by

15% or more, then you might have a bad capacitor.


7. Before disconnecting the capacitors, note the location of all the cables

and mark them accordingly.


8. Disconnect power cables/bus bars from the capacitor terminals on all

four bushings and isolate them from the capacitor. (Refer to “Filter
Capacitor Replacement” guidelines in the Classic User Manual -
Component Definition and Maintenance chapter (chapter 6) for using
proper torque when reconnecting the capacitors)


Second

Method

1. Ensure there is no power to the equipment before testing the

capacitor.

A T T E N T I O N

A T T E N T I O N

To prevent electrical shock ensure the main
power has been disconnected before working on
the capacitor. Verify that all circuits are voltage
free using a hot stick or appropriate voltage-
measuring device. Failure to do so may result in
injury or death.

D.C. Link / Fan / Control
Components (cont.)