Drive configurations – powerflex 7000 “a” frame – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control (PanelView 550) User Manual

Page 14

Advertising
background image

1-2

Overview of Drive

7000A-UM151D-EN-P – March 2013

7000 “A” Frame


Drive Configurations – PowerFlex 7000 “A” Frame

Configuration #1

Direct-to-Drive

(AFE with DTC DC Link)

Elimination of isolation transformer results in lower

losses and saved space

An integrated system solution for fewer connections

and reduced installation costs

New or existing motors

Small system footprint

3 cables in/3 cables out on entire system for easy

installation

Low line harmonics and high power factor (typical

current THD < 5%, PF > 0.98)

Fan control power and control circuit power

supplied internally

Input starter optional

Direct-

to-Drive

(Optional

Input

Starter)

Configuration #2

AFE Rectifier

(Separate isolation transformer)

Optimum installation flexibility with connection to

indoor or outdoor isolation transformers

Compact packaging for smallest footprint

requirements

New or existing motors

3 cables in/3 cables out for easy installation

Low line harmonics and high power factor (typical

current THD < 5%, PF > 0.98)

Fan control power supplied internally (1-phase

control circuit power supplied by customer,
120V/60 Hz, 110V/50 Hz, 20 amp)

AFE

Rectifier

Configuration #3

AFE Rectifier

(Integral isolation transformer)

An integrated system solution for fewer connections

and reduced installation costs

Small system footprint

New or existing motors

3 cables in/3 cables out for easy installation

Integral cooling fans for VFD and transformer

Low line harmonics and high power factor (typical

current THD < 5%, PF > 0.98)

Fan control power supplied internally (1-phase

control circuit power supplied by customer,
120V/60 Hz, 110V/50 Hz, 20 amp)

Integral

Isolation

Transformer

Advertising