Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control (PanelView 550) User Manual
Page 47

Drive Installation
2-25
7000 “A” Frame
7000A-UM151D-EN-P – March 2013
Cable
Insulation
The cable insulation requirements for the PowerFlex 7000 “A”
Frame drive are given in the tables below.
A T T E N T I O N
A T T E N T I O N
Voltage ratings shown in the following
tables are peak line-to-ground. Some cable
manufacturers rate voltage line-to-line RMS.
Ensure the cable meets the rating specified
in the following tables.
Cable Insulation Requirements for AFE Drives with Separate Isolation Transformer
System Voltage (V, RMS)
Cable Insulation Rating (kV)
(Maximum Peak Line-to-Ground)
Machine Side
2400
≥ 4.1
≥ 2.2
3000
≥ 5.12
≥ 2.75
3300
≥ 5.63
≥ 3.0
4160
≥ 7.1
≥ 3.8
6000
≥ 10.8
≥ 5.5
6300
≥ 11.4
≥ 5.8
6600
≥ 11.8
≥ 6.0
Cabling from secondary side of Isolation Transformer to input of VFD
Cable Insulation Requirements for “Direct-to-Drive” Technology or Integral
Isolation Transformer
System Voltage (V, RMS)
Cable Insulation Rating (kV)
(Maximum Peak Line-to-Ground)
Line Side
Machine Side
2400
≥ 2.2
≥ 2.2
3000
≥ 2.75
≥ 2.75
3300
≥ 3.0
≥ 3.0
4160
≥ 3.8
≥ 3.8
6000
≥ 5.5
≥ 5.5
6300
≥ 5.8
≥ 5.8
6600
≥ 6.0
≥ 6.0