Drive Installation

2-25

7000 “A” Frame

7000A-UM151D-EN-P – March 2013

Cable

Insulation

The cable insulation requirements for the PowerFlex 7000 “A”
Frame drive are given in the tables below.

A T T E N T I O N

A T T E N T I O N

Voltage ratings shown in the following
tables are peak line-to-ground. Some cable
manufacturers rate voltage line-to-line RMS.
Ensure the cable meets the rating specified
in the following tables.

Cable Insulation Requirements for AFE Drives with Separate Isolation Transformer

System Voltage (V, RMS)

Cable Insulation Rating (kV)

(Maximum Peak Line-to-Ground)

Machine Side

2400

≥ 4.1

≥ 2.2

3000

≥ 5.12

≥ 2.75

3300

≥ 5.63

≥ 3.0

4160

≥ 7.1

≥ 3.8

6000

≥ 10.8

≥ 5.5

6300

≥ 11.4

≥ 5.8

6600

≥ 11.8

≥ 6.0

Cabling from secondary side of Isolation Transformer to input of VFD


Cable Insulation Requirements for “Direct-to-Drive” Technology or Integral
Isolation Transformer

System Voltage (V, RMS)

Cable Insulation Rating (kV)

(Maximum Peak Line-to-Ground)

Line Side

Machine Side

2400

≥ 2.2

≥ 2.2

3000

≥ 2.75

≥ 2.75

3300

≥ 3.0

≥ 3.0

4160

≥ 3.8

≥ 3.8

6000

≥ 5.5

≥ 5.5

6300

≥ 5.8

≥ 5.8

6600

≥ 6.0

≥ 6.0