2-34

Drive Installation

7000A-UM151D-EN-P – March 2013

7000 “A” Frame


Grounding Practices

The purpose of grounding is to:

• provide for the safety of personnel

• limit dangerous voltages on exposed parts with respect to ground

• facilitate proper over current device operation under ground fault

conditions, and

• provide for electrical interference suppression


Generally, the means used for external grounding
of equipment should be in accordance with the
Canadian Electrical Code (CEC), C22.1 or the
National Electrical Code (NEC), NFPA 70 and
applicable local codes.


Refer to the grounding diagrams that follow for ground connections.
The drive’s main ground bus must be connected to the system
ground. This ground bus is the common ground point for all grounds
internal to the drive.

ISOLATION

TRANSFORMER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

Connected to the neutral point
of the output capacitor

OUTPUT

GROUND

NETWORK

Figure 2.23 – Ground Connection Diagram with Isolation Transformer

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

AC LINE

REACTOR

TRANSFORMER

Connected to the neutral point
of the output capacitor

GROUND

FILTER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

AC LINE

REACTOR

TRANSFORMER

Connected to the neutral point
of the output capacitor

GROUND

FILTER

Figure 2.24 – Ground Connection Diagram with Line Reactor