B-6

Catalog Number Explanation – Drive Selection

7000A-UM151D-EN-P – March 2013

7000 “A” Frame

Table B-5 – Typical Application Load Torque Profiles *

Application

Load

Torque

Profile

Load Torque as Percent

of Full-Load Drive Torque

Required Drive

Service

Duty Rating

Tachometer

Required for Extra

Starting Torque?

Break-away Accelerating Peak Running

Agitators
Liquid

CT

100

100

100

Heavy

Yes

Slurry CT

150

100

100

Heavy

Yes

Blowers ( Centrifugal)
Damper Closed

VT

30

50

40

Normal

No

Damper

Open

VT

40 110 100 Normal

No

Chipper ( Wood) Starting Empty

CT

50 40 200

Contact

Factory

No

Compressors
Axial-vane,

Loaded

VT

40 100 100 Normal

No

Reciprocating, start unloaded

CT

100

50

100

Normal

Yes

Conveyors
Belt type, loaded

CT

150

130

100

Heavy

Yes

Drag type

CT

175

150

100

Contact Factory

Yes

Screw type, loaded

CT

200

100

100

Contact Factory

Yes

Extruders (Rubber or Plastic)

CT 150 150 100

Contact

Factory Yes

Fans ( Centrifugal, ambient)
Damper closed

VT

25

60

50

Normal

No

Damper

open

VT

25 110 100 Normal

No

Fans ( Centrifugal, hot gases)
Damper

closed

VT

25 60 100 Normal No

Damper

open

VT

25 200 175

Contact

Factory

No

Fans ( Propeller, axial flow)

VT

40 110 100 Normal

No

Kilns ( Rotary, loaded)

CT 250 125 125

Contact

Factory Yes

Mixers
Chemical CT

175

75

100

Contact

Factory

Yes

Liquid CT

100

100

100

Heavy

Yes

Slurry CT

150

125

100

Heavy

Yes

Solids CT

175

125

175

Contact

Factory

Yes

Pulper

VT

40 100 150

Contact

Factory

No

Pumps
Centrifugal, Discharge open

VT

40

100

100

Normal

No

Oil field Flywheel

CT

150

200

200

Contact Factory

Yes

Propeller

VT

40 100 100 Normal

No

Fan

Pump

VT

40 100 100 Normal

No

Reciprocating / Positive Displacement

CT

175 30 175

Contact

Factory

Yes

Screw type, started dry

VT

75

30

100

Normal

No

Screw type, primed, discharge open

CT

150

100

100

Heavy

Yes

Slurry handling, discharge open

CT

150

100

100

Heavy

Yes

Turbine, Centrifugal, deep-well

VT

50

100

100

Normal

No

Vane-type, positive displacement

CT

150

150

175

Contact Factory

Yes

Separators, air ( fan type )

VT

40 100 100 Normal

No

* NOTE: PowerFlex 7000 “A” Frame suitable only for normal duty service rating.