Drive Installation

2-33

7000 “A” Frame

7000A-UM151D-EN-P – March 2013

Power and Control Wiring

Drive line-ups (i.e. Drive and Input Starter) which are delivered in
two or more sections, for ease of handling, will require that the
power and control wiring be re-connected. After the sections are
brought together, the power and control wiring is to be re-connected
as per the schematic drawings provided.

Control

Cables


Control cable entry/exit should be located near the terminal block
'TBC' – the customer's connections are to be routed along the
empty side of the TBC terminals. These terminals are sized to
accept a maximum #14 AWG. The low voltage signals (includes
4-20mA) are to be connected using twisted shielded cable, with a
minimum #18 AWG.


Of special concern is the tachometer signal. Two tachometer inputs
are provided to accommodate a quadrature tachometer (senses motor
direction). The tachometer power supply is isolated and provides
+15 Volts and a ground reference. Many tachometer outputs have an
open collector output, in which case a pull-up resistor must be added
to ensure that proper signals are fed to the system logic. (Refer to
Appendix A "When is a Tachometer Required?" to see if one
needs to be supplied.)


Low voltage signals are to be connected using
twisted shielded cable with the shield connected
at the signal source end only. The shield at the
other end is to be wrapped with electrical tape
and isolated. Connections are to be made as
shown on the electrical drawings (ED) provided.


I M P O R T A N T

I M P O R T A N T