Drive Installation

7000A-UM151D-EN-P – March 2013

7000 “A” Frame

Installation

When the drive has been placed at its installation area, the lag bolts
that fasten the shipping skid to the drive must be removed. The drive
is moved off the shipping skid and the shipping skid can be
discarded.


Position the drive in its desired location. Verify that the drive is on a
level surface and that the position of the drive will be vertical when
the anchor bolts are installed.


The location of the anchor points is provided with the dimension
drawing of the drive.


Install and tighten the anchor bolts. (M12 or ½” hardware required).
Engineering bolt systems are required for seismic requirements.
Consult factory.


Remove the top lifting angles, retain the hardware.


Install the hardware from the lifting angles in the tapped holes at the
top of drive; this prevents leakage of cooling air as well as keeping
dust out of the equipment.



Installation of Exhaust Air Hood


On the top of the cabinet with the cooling fan, a sheet metal exhaust
hood is to be installed. The components to make up the exhaust
hood have been packaged and shipped with the drive. (For drives
with an acoustic hood, the components are shipped assembled. See
Figure 2.2)


The first step is to remove the protective plate covering the fan
opening on the drive. It is a flat cover plate bolted to the top plate.
Remove the bolts and plate and set aside for re-use.


Secondly, loosely assemble the two L-shaped panel components
shipped with the drive as per Figure 2.1.