Troubleshooting the Kinetix 5500 Drive System

FLT S18 – CONV OVERTEMP FL

Converter OverTemp
Factory Limit Fault

The measured converter temperature has exceeded
the factory set temperature limit.

• Reduce acceleration times of all drives sharing the DC bus
• Reduce number of shared DC follower drives
• Modify the command profile to reduce speed or increase time
• Reduce drive ambient temperature
• Verify airflow through drive is not obstructed

FLT S20 – CONV OVERLOAD FL

Converter Thermal Overload
Factory Limit Fault

The converter thermal model indicates that the
temperature has exceeded the factory set capacity
rating of 110%.

• Reduce acceleration times of all drives sharing the DC bus
• Reduce number of shared DC follower drives
• Reduce duty-cycle of commanded motion

FLT S21 – CONV OVERLOAD UL

Converter Thermal Overload
User Limit Fault

The converter thermal model indicates that the
temperature has exceeded the limit given by
Converter Thermal Overload User Limit.

• Reduce acceleration times of all drives sharing the DC bus
• Reduce number of shared DC follower drives
• Reduce duty-cycle of commanded motion
• Increase the Converter Thermal Overload UL attribute value

FLT S23 – AC PHASE LOSS

AC Single Phase Loss Fault

A single AC input phase was lost while the drive was
enabled.

Check AC input voltage on all phases.

FLT S25 – PRECHARGE FAILURE

Pre-charge Failure Fault

The pre-charge circuit monitoring algorithm detected
that the DC bus did not reach a factory set voltage
level after charging for a period of time.

• Check AC input voltage on all phases
• Check input power wiring
• Replace drive if fault persists

FLT S29 – BUS REG OVERLOAD FL

Bus Regulator Thermal Overload
Factory Limit Fault

The shunt thermal model has exceeded its factory set
thermal capacity limit.

• Modify the duty cycle of the application
• Add external shunt for additional capacity
• Add capacitor module if needed

FLT S30 – BUS REG OVERLOAD UL

Bus Regulator Thermal Overload
User Limit Fault

The shunt thermal model has exceeded the thermal
capacity limit given by Bus Regulator Thermal
Overload User Limit.

• Modify the duty cycle of the application
• Add external shunt for additional capacity
• Increase the Bus Regulator Thermal Overload UL attribute value
• Add capacitor module if needed

FLT S31 – BUS REG FAILURE

Bus Regulator Failure

The shunt driver IC has detected that the shunt
resistor is shorted.

• Check for shorts in the shunt connector
• Unplug the shunt connector and measure the resistance of the

shunt

• Replace drive if shunt resistor is shorted

FLT S33 – BUS UNDERVOLT FL

Bus Undervoltage
Factory Limit Fault

DC Bus voltage level is below the factory set limit as
determined by the configured input voltage.

• Verify voltage level of the incoming AC
• Monitor AC power source for glitches or line droop
• Install UPS on AC input

FLT S34 – BUS UNDERVOLT UL

Bus Undervoltage
User Limit Fault

DC Bus voltage level is below the user set limit as
given by Bus Undervoltage User Limit.

• Verify voltage level of the incoming AC
• Monitor AC power source for glitches or line droop
• Install UPS on AC input
• Increase Bus Undervoltage UL attribute value

FLT S35 – BUS OVERVOLT FL

Bus Overvoltage
Factory Limit Fault

DC Bus voltage level is above the factory set limit as
determined by the configured input voltage.

• Change the deceleration or motion profile of all drives connected to

the DC bus

• Unplug the shunt connector and measure the resistance of the

shunt

• Replace drive if shunt resistor is open

FLT S39 – BUS POWER LEAK

Bus Power Leakage Fault

Measured converter power exceeded estimated
inverter output power by more than a factory limit.

• Check bus power sharing configuration attribute
• Check AC input and DC bus sharing connections

FLT S45 – FDBK COMM FL

Motor Feedback Data Loss
Factory Limit Fault

The number of consecutive missed or corrupted serial
data packets from the intelligent feedback device has
exceeded a factory set limit.

• Check motor feedback cable and connector
• Check motor power cable and feedback wire shields are secured

correctly

• Check motor frame is grounded correctly

Table 56 - FLT Sxx Fault Codes (continued)

Exception Code on Display

Exception Text

Problem

Possible Solutions