Kinetix 5500 Safe Torque-off - Hardwired Safety

Chapter 9

Figure 66 - System Operation when Inputs are Meeting Timing Requirements

Troubleshoot the Safe Torque-off Function

Table 73 - 2198-Hxxx-ERS Servo Drive Troubleshooting

ATTENTION: If any of the safety enable inputs de-energize, the Start Inhibit
field indicates SafeTorqueOffInhibit and GuardStopRequestStatus bit of
AxisGuardStatus tag set to 1. Both inputs must be de-energized within 1 second
and re-energized within 1 second to avoid GuardStopInputFault conditions.

24V DC

24V DC

0V DC

0V DC

1

1

0

0

100 ms

1 Second

1

2 3

4

5

6

GuardStopRequestStatus

GuardStopInputFault

SS_IN_CH0

SS_IN_CH1

Event

Description

1

At least one input is switched-off. GuardStopRequestStatus bit is set to 1.

2

Second input is switched-off within 1 second. This event must always occur prior to Event 3 to prevent
GuardStopInputFault.

3

First input is switched-on.

4

Second input is switched-on within 1 second of event 3.

5

Both inputs are in OFF state simultaneously within 1 second. As a result, GuardStopInputFault is not posted.

6

GuardStopRequestStatus bit sets back to 0 if event 4 occurred within 100 ms interval after event 3. If event 4
is outside of the 100 ms interval and within the 1 second (event 3) interval, then GuardStop RequestStatus
bit sets back to 0 after the 1 second interval following event 3.

Exception Code on Drive Display

Fault Message
Logix Designer

Problem

Possible Solutions

SAFE FLT 09 - SS IN

GuardStopInputFault

Safe torque-off function
mismatch. System does not
allow motion. Safe torque-
off mismatch is detected
when safety inputs are in a
different state for more
than 1.0 second.

Verify safety wiring and connections:

Wire terminations at safe torque-

off (STO) connector

Cable/header not seated correctly
+24V power

Check state of safety inputs.
Reset error and run proof test.
If error persists, return the drive to

Rockwell Automation.