Rockwell Automation Publication 2198-UM001D-EN-P - May 2014

35

Planning the Kinetix 5500 Drive System Installation

Chapter 2

Table 14 - Power Dissipation Specifications

Minimum Clearance Requirements

This section provides information to assist you in sizing your cabinet and
positioning your Kinetix 5500 drive:

Additional clearance is required for cables and wires or the shared-bus

connection system connected to the top of the drive.

Additional clearance is required if other devices are installed above and/or

below the drive and have clearance requirements of their own.

Additional clearance left and right of the drive is required when mounted

adjacent to noise sensitive equipment or clean wire ways.

The recommended minimum cabinet depth is 300 mm (11.81 in.).

Figure 12 - Minimum Clearance Requirements

Kinetix 5500 Drive
Cat. No.

Frame
Size

Usage as % of Rated Power Output

(watts)

20%

40%

60%

80%

100%

2198-H003-ERSx

1

12

25

37

50

62

2198-H008-ERSx

2198-H015-ERSx

2

40

80

120

160

200

2198-H025-ERSx

2198-H040-ERSx

2198-H070-ERSx

3

64

128

192

256

320

Clearance right of the
drive is not required.

Clearance left of the

drive is not required.

Kinetix 5500

Servo Drive

40 mm (1.57 in.) clearance below

drive for airflow and installation.

40 mm (1.57 in.) clearance above

drive for airflow and installation.

Refer to the Kinetix Servo Drives

Technical Data, publication

GMC-TD003

,

for Kinetix 5500 drive dimensions.

IMPORTANT

Mount the drive in an upright position as shown. Do not mount the drive on its side.