Figure 54, And r – Rockwell Automation 2198-Hxxx Kinetix 5500 Servo Drives User Manual User Manual

Page 94

Advertising
background image

94

Rockwell Automation Publication 2198-UM001D-EN-P - May 2014

Chapter 5

Connecting the Kinetix 5500 Drive System

Table 47 - 2090-CFBM7DF-CEAxxx Feedback Cables

A mounting bracket is included with the 2198-H2DCK converter kit to secure
the kit to the drive. Install the mounting bracket in the mounting position
specific to the frame size of your drive.

Figure 54 - Wiring the 2198-H2DCK Feedback Converter Kit

Rotary Motors

MPL-B15xxx…MPL-B2xxx-V/Ex4/7xAA
MPF/MPS-Bxxx
-M/S
MPF-A5xxx
-M/S

MPL-A15xxx…MPL-A2xxx-V/Ex4/7xAA
MPF/MPS-A3xx
-M/S
MPF/MPS-A4xx
-M/S
MPF/MPS-A45xx
-M/S
MPS-A5xxx
-M/S
MPL-A3xxx
-M/Sx7xAA
MPL-A4xxx
-M/Sx7xAA
MPL-A45xxx
-M/Sx7xAA
MPM-A115xxx
…MPM-A130xxx-M/S

2198-H2DCK
Converter Kit Pin

MPL-B3xxx…MPL-B6xxx-M/Sx7xAA
MPL-A5xxx
-M/Sx7xAA
MPM-A165xxx
…MPM-A215xxx
MPM-Bxxxxx-M/S

Linear Actuators

MPAS-Bxxxxx-VxxSxA
MPAR-Bxxxx,
MPAI-Bxxxx
LDAT-Sxxxxxx-xDx

MPAS-Axxxxx-VxxSxA
MPAR-Axxxx,
MPAI-Axxxx

1

Sin+

Sin+

1

2

Sin-

Sin-

2

3

Cos+

Cos+

3

4

Cos-

Cos-

4

5

Data+

Data+

5

6

Data-

Data-

10

9

Reserved

EPWR_5V

14

10

ECOM

ECOM

6

(1)

11

EPWR_9V

Reserved

7

12

ECOM

ECOM

6

13

TS+

TS+

11

(1) The ECOM and TS- connections are tied together and connect to the cable shield.

14

11

10

7

6

5

4

3

2

1

2
1

Shield Clamp

Clamp Screws (2)

Service Loops

Tie Wrap for Stress Relief
and Wire Management

Mounting Screws (2)

Mounting Bracket

Frame 2 Mounting Position

(catalog numbers 2198-H015-ERSx,

2198-H025-ERS, and 2198-H040-ERSx)

Frame 1 Mounting Position

Frame 3 Mounting Position

(catalog number 2198-H070-ERSx)

(catalog numbers 2198-H003 ERSx
and 2198-H008-ERSx)

Refer to Hiperface to DSL Feedback Converter Kit Installation Instructions,

publication

2198-IN006

, for converter kit specifications.

10-pin
Connector

Converter Kit Mounting Hole

with Protective Cover Removed
(frame 1 drive example shown)

1. Place exposed cable shield

in the channel.

2. Place the shield clamp over

the exposed shield.

3. Tighten screws, torque

0.3 N•m (2.6 lb•in).

Exposed Shield

Aligned

in the Cable Channel