Kinetix 5500 Safe Torque-off - Hardwired Safety

Figure 67

demonstrates when the safe torque-off mismatch is detected and a

GuardStopInputFault is posted.

Figure 67 - System Operation in the Event that the Safety Enable Inputs Mismatch

When one safety input is turned off, the second input must also be turned off,
otherwise a fault is asserted (see

Figure 68

). The fault is asserted even if the first

safety input is turned on again.

Figure 68 - System Operation in the Event that the Safety Enable Inputs Mismatch Momentarily

ATTENTION: The safe torque-off fault is detected upon demand of the safe
torque-off function. After troubleshooting, a safety function must be executed
to verify correct operation.

IMPORTANT

The Safe Torque Off fault can be reset only if both inputs are in the Off-state for
more than 1 second. After the fault reset requirement is satisfied, an MASR
command in the Logix Designer application must be issued to reset the
GuardStopInputFault.

24V DC

24V DC

0V DC

0V DC

1

1

0

0

1 Second

SafeTorqueOffInhibit

GuardStopInputFault

SS_IN_CH0

SS_IN_CH1

24V DC

24V DC

0V DC

0V DC

1

1

0

0

1 Second

SafeTorqueOffInhibit

GuardStopInputFault

SS_IN_CH0

SS_IN_CH1