Appendix D Home to Torque-level Example

Potential for Position Error

When executing a torque limit homing procedure there is potential for a position
error. As mentioned earlier, for the home to torque limit to complete, the output
torque to the motor must reach or exceed the specified torque level for a set time
of 500 ms. During this time the axis is against the mechanical hard-stop, and
following error is increasing in the position loop. If the Position Error Tolerance
value is exceeded before completion of the homing instruction, a Position Error
(E19) results.

There are two methods to limit the occurrence of an E19.

Set the Position Error Tolerance value on the Limits tab of the Axis

Properties to 10 mm.

Modify the Position Error Tolerance value to 10 mm using a SSV

instruction code. You can use code similar to the code on

page 122

which is

used to change the Bipolar Torque Limit.

Rung 6 of the ladder code opens the Position Error window. This lets the
Homing complete without causing a Position Error. The original value is reset
after Homing completes.

TIP

The second method is preferred because it temporarily sets Position
Error Tolerance to a value appropriate for homing to a mechanical
hard-stop and then resets it to the original value set in the Axis
Properties dialog box.