Ball screw drive stages – Rockwell Automation MPMA Integrated Multi-Axis Linear Stages User Manual

Page 51

Advertising
background image

Rockwell Automation Publication MPMA-UM001B-EN-P - November 2010

51

Configuration Guidelines

Chapter 6

Ball Screw Drive Stages

Enter these parameters in the Axis Properties tab of RSLogix 5000 software for
ball screw linear stages, catalog number MPAS-

xxxxxx-Vxxxxx.

Axis Properties Tab

Parameter

Entry/Selection, with applicable distance unit settings

Metric

English

Drive/Motor

Motor Catalog Number

Select one from the list
MPAS-Axxxx1-V05S2x
MPAS-Axxxx1-V05S4x
MPAS-Axxxx2-V20S2x
MPAS-Axxxx2-V20S4x
MPAS-Bxxxx1-V05S2x
MPAS-Bxxxx1-V05S4x
MPAS-Bxxxx2-V20S2x
MPAS-Bxxxx2-V20S4x

Drive Resolution

200,000

Drive Counts per

Motor Millimeter

Conversion Positioning

Mode

Linear

ATTENTION: Setting the Positioning Mode to Rotary can cause damage to the
stage or the machine due to incorrect positioning.

Conversion Constant
Test Increment

10,000 drive counts / 1.0 mm for

254,000 drive counts / 1.0 in. for

Hookup

5 mm min

0.2 in., min

Drive Polarity

Positive

Homing Mode Active

Position 0

(or

programmable)

Offset

5 mm, min

0.2 in., min

Sequence Torque

Level-to-marker

Direction Reverse

Bi-directional

Torque Level

50%, min
Greater if the system friction, force, or weight exceeds 50% of the Continuous Force Rating at any
point in the range of motion.

Speed 50 mm/s

1.97 in./s

Return Speed

10 mm/s

0.39 in./s

Absolute Home is available for ball screw linear stages. For maximum range of motion, position the carriage so its proximal
edge is 25.4 mm (1.0 in.) from the inside edge of the end plate.

(+)

(-)

Positive Direction