Configuring the Interbus Module

4-3

Step 2.

If Logic Command/Reference is enabled, configure the
parameters in the drive to accept the Logic and Reference
from the module. For example, set Speed Ref A Sel (90)
in an SP600 drive to “Network” so that the drive uses the
Reference from the module. Also, verify that the mask
parameters (for example, Manual Mask (286)) in the drive
are configured to receive the desired logic from the
module.

Step 3.

If you enabled one or more Datalinks, configure
parameters in the drive to determine the source and
destination of data in the Datalink(s). Also, ensure that the
Interbus module is the only module using the enabled
Datalink(s).

Step 4.

Interbus requires the network I/O mapping to be
configured first in the module. CMD software will read this
configuration online when it is configuring the scanner.

Process Input Data Description (PIDD) words map input
data on the network (data seen as inputs to the scanner
and controller program). Example input data includes
Logic Status, Feedback and Datalinks (Datalink x1 Out).
Up to 9 words of input data can be mapped.

Process Output Data Description (PODD) words map
output data on the network (data sent as outputs from the
scanner and controller program). Example output data
includes Logic Command, Reference and Datalinks
(Datalink x1 In). Up to 9 words of output data can be
mapped.

Table 4.2 lists the indexes used to select the I/O data.

Table 4.2 – PIDD / PODD Indexes

Input

Output

Value
(Hex)

Value
(Dec)

Selects

Value
(Hex)

Value
(Dec)

Selects

2F9A

12186

Logic Status

2F98

12184

Logic
Command

2F9B

12187

Feedback

2F99

12185

Reference

2FA4

12196

Datalink A1 Out 2F9C 12188

Datalink A1 In

2FA5

12197

Datalink A2 Out 2F9D 12189

Datalink A2 In

2FA6

12198

Datalink B1 Out 2F9E

12190

Datalink B1 In

2FA7

12199

Datalink B2 Out 2F9F

12191

Datalink B2 In

2FA8

12200

Datalink C1 Out 2FA0

12192

Datalink C1 In

2FA9

12201

Datalink C2 Out 2FA1

12193

Datalink C2 In

2FAA

12202

Datalink D1 Out 2FA2

12194

Datalink D1 In

2FAB

12203

Datalink D2 Out 2FA3

12195

Datalink D2 In