Rockwell Automation RECOMM-IBUS Interbus Communications Module User Manual
Page 39
Configuring the Interbus Scanner
5-9
Step 13. Right-click on the SST-IBS-SLC scanner and select
Process Data. This shows the Interbus I/O mapping for
each device on the network, as shown in figure 5.12.
In the example, the length is 144 bits (9 words) because the
RECOMM-IBUS was previously configured for the maximum I/O
configuration. (See section 4.3, Setting the I/O Configuration.
Depending on your application needs, this length may be less.)
The scanner mapping correlates to SLC addressing as shown in
figure 5.13.
Figure 5.12 – Sample Interbus I/O Mapping
Figure 5.13 – Scanner Mapping / SLC Addressing
(USC/4) Output SLC (USC/4) Input SLC
0
1
63
64
65
511
O:x.0(high)
O:x.0(low)
O:x.31(low)
M0:x.0(high)
M0:x.0(low)
M0:x.223(low)
512
513
575
576
1023
I:x.0(high)
I:x.0(low)
I:x.31(low)
M1:x.0(high)
M1:x.0(low)
M1:x.223(low)
Scanner
Scanner