8 viewing and clearing events – Rockwell Automation RECOMM-IBUS Interbus Communications Module User Manual
Page 87

Troubleshooting the Interbus Module and Network
8-5
8.8
Viewing and Clearing Events
The module maintains an event queue that reports the history of its
actions. You can view the event queue using an LCD OIM or
VS Utilities software.
To View and Clear Events Using an LCD OIM
Use the procedure shown in figure 8.2 to access the event queue
using the LCD OIM. Note that you must have the RECOMM-IBUS
module as the selected device to access the event queue.
24
DPI Rx Err Cntr
The current value of the DPI CAN Receive error
counter.
25
DPI Tx Err Cntr
The current value of the DPI CAN Transmit error
counter.
26
IbusImage Siz
Amount of process data bytes used on the Interbus
network by the module.
Table 8.6 – Module Diagnostic Items (Continued)
No.
Event
Description
Figure 8.2 – VIewing and Clearing Events Using an LCD OIM
Diagnostics:
Device Version
OIM Version
View Event Queue
P 5 : R E C O M M - I B U S
Stopped Auto
Main Menu
Diagnostics
EvtQ# : E#xxxxx
Online @ 500kbps
1
Clrqu
Highlight Diagnostics icon
Highlight item
Monitor
L a n g
> >
Press F2 key to
clear event queue