Troubleshooting the Interbus Module and Network

8-5

8.8

Viewing and Clearing Events

The module maintains an event queue that reports the history of its
actions. You can view the event queue using an LCD OIM or
VS Utilities software.

To View and Clear Events Using an LCD OIM

Use the procedure shown in figure 8.2 to access the event queue
using the LCD OIM. Note that you must have the RECOMM-IBUS
module as the selected device to access the event queue.

24

DPI Rx Err Cntr

The current value of the DPI CAN Receive error
counter.

25

DPI Tx Err Cntr

The current value of the DPI CAN Transmit error
counter.

26

IbusImage Siz

Amount of process data bytes used on the Interbus
network by the module.

Table 8.6 – Module Diagnostic Items (Continued)

No.

Event

Description

Figure 8.2 – VIewing and Clearing Events Using an LCD OIM

Diagnostics:

Device Version

OIM Version

View Event Queue

P 5 : R E C O M M - I B U S

Stopped Auto

Main Menu

Diagnostics

EvtQ# : E#xxxxx
Online @ 500kbps

1

Clrqu

Highlight Diagnostics icon

Highlight item

Monitor

L a n g

> >

Press F2 key to

clear event queue