Troubleshooting the Interbus Module and Network

8-3

8.5

Bus Active (BA) Status Indicator

8.6

Bus Voltage (UL) Status Indicator

8.7

Module Diagnostic Items

Module Diagnostic Items can be viewed using VS Utilities software
or an LCD OIM. Diagnostic items show current data being
transmitted and received by the Host device (e.g., drive), and other
diagnostic information regarding the RECOMM-IBUS module.

Table 8.4 – Bus Active (BA) Status Indicator: State Definitions

Status

Cause

Corrective Actions

Off

Bus not active.

Set master to start data
transmission.

Solid
Green

Bus active,
exchanging data.

No action required.

Flash
Green

Bus active, but no
data exchange.

Set master to start data
transmission.

Table 8.5 – Bus Voltage (UL) Status Indicator

1

: State Definitions

1

LED is visible only when the drive cover is open.

Status

Cause

Corrective Actions

Off

Bus voltage is not OK.

Securely connect the module to
the drive using the Internal
interface cable

Apply power to the drive.

Solid
Green

Bus active.

No action required.

Table 8.6 – Module Diagnostic Items

No.

Event

Description

1

Common Logic
Cmd

The current value of the Common Logic Command
being transmitted to the Host.

2

Prod Logic Cmd The current value of the Product-Specific Logic

Command being transmitted to the Host.

3

Reference

The current value ofthe Product-Specific Reference
being transmitted to the Host.

4

Common Logic
Sts

The current value of the Product-Specific Logic
Status being received from the Host.