Rockwell Automation RECOMM-IBUS Interbus Communications Module User Manual

Page 98

Advertising
background image

B-6

Interbus Communications Module

Sets the Reference data that is sent to the drive if any of the
following is true:

• Comm Flt Action (6) is set to Send Flt Cfg and communications

are disrupted.

• Idle Flt Action (7) is set to Send Flt Cfg and the scanner is put into

Program mode.

Important: If the drive uses a 16-bit Reference, the most significant

word of this value must be set to zero (0) or a fault will
occur.

Sets the data that is sent to the Datalink in the drive if any of the
following is true:

• Comm Flt Action (6) is set to Send Flt Cfg and communications

are disrupted.

• Idle Flt Action (7) is set to Send Flt Cfg and the scanner is put into

Program mode.

11

Flt Cfg Ref

Range:

0 to 4294967295

Default:

0

Type:

Read/Write

Reset Required: No

12
13
14
15
16
17
18
19

Flt Cfg A1
Flt Cfg A2
Flt Cfg B1
Flt Cfg B2
Flt Cfg C1
Flt Cfg C2
Flt Cfg D1
Flt Cfg D2

Range:

0 to 4294967295

Default:

0

Type:

Read/Write

Reset Required: No