2 setting the fault configuration parameters – Rockwell Automation RECOMM-IBUS Interbus Communications Module User Manual

Page 26

Advertising
background image

4-6

Interbus Communications Module

4.4.2 Setting the Fault Configuration Parameters

If you set Comm Flt Action (6) to “Send Flt Cfg,” the values in the
following parameters are sent to the drive after a communications
fault occurs. You must set these parameters to values required by
your application.

Changes to these parameters take effect immediately. A reset is not
required.

Table 4.5 – Fault Configuration Parameters

Number

Name

Description

10

Flt Cfg Logic A 16-bit value sent to the drive for Logic

Command.

11

Flt Cfg Ref

A 32-bit value (0 – 4294967295) sent to
the drive as a Reference or Datalink.
Important: If the drive uses a 16-bit
Reference or 16-bit Datalinks, the most
significant word of the value must be set
to zero (0) or a fault will occur.

12 – 19

Flt Cfg x1 In