5 viewing the module configuration – Rockwell Automation RECOMM-IBUS Interbus Communications Module User Manual

Page 28

Advertising
background image

4-8

Interbus Communications Module

4.5

Viewing the Module Configuration

The parameters in table 4.6 provide information about how the
module is configured. You can view these parameters at any time.

Table 4.6 – Module Configuration Status Parameters

No.

Name and Description

Details

01

DPI Port
Port to which the module is connected. This will
usually be port 5.

Default:

0

Minimum:

0

Maximum:

7

Type:

Read Only

03

Ref/Fdbk Size
Size of the Reference/Feedback. The drive
determines the size of the Reference/Feedback.

Default:

0 = 16-bit

Values:

0 = 16-bit
1 = 32-bit

Type:

Read/Write

04

Datalink Size
Size of each Datalink word. The drive determines
the size of Datalinks.

Default:

0 = 16-bit

Values:

0 = 16-bit
1 = 32-bit

Type:

Read Only

09

DPI I/O Active
I/O that the module is actively transmitting. The
value of this parameter will usually be equal to the
value of parameter 8 - DPI I/O Config.

Default:

xxx0 0001

Bit Values:

0 = I/O disabled
1 = I/O enabled

Type:

Read Only

Bit Definitions
0 = Cmd/Ref
1 = Datalink A
2 = Datalink B
3 = Datalink C
4 = Datalink D
5 = Not Used
6 = Not Used
7 = Not Used

21

PIDD W0 Actual
Actual Process Input Description for Word 0
Displays the Actual PIDD Config being transmitted
to word 0 in the Interbus Master.

Value:

See table 4.2

Type:

Read Only

23

PIDD W1 Actual
Actual Process Input Description for Word 1
Displays the Actual PIDD Config being transmitted
to word 1 in the Interbus Master.

Value:

See table 4.2

Type:

Read Only

25

PIDD W2 Actual
Actual Process Input Description for Word 2
Displays the Actual PIDD Config being transmitted
to word 2 in the Interbus Master.

Value:

See table 4.2

Type:

Read Only

27

PIDD W3 Actual
Actual Process Input Description for Word 3
Displays the Actual PIDD Config being transmitted
to word 3 in the Interbus Master.

Value:

See table 4.2

Type:

Read Only

29

PIDD W4 Actual
Actual Process Input Description for Word 4
Displays the Actual PIDD Config being transmitted
to word 4 in the Interbus Master.

Value:

See table 4.2

Type:

Read Only

31

PIDD W5 Actual
Actual Process Input Description for Word 5
Displays the Actual PIDD Config being transmitted
to word 5 in the Interbus Master.

Value:

See table 4.2

Type:

Read Only

Bit

Default

1

0

0

0

0

x x

x

0

1

2

3

4

5

7

6