Rockwell Automation Publication MP-UM001D-EN-P - September 2013

49

Configuration Guidelines

Chapter 6

2. Set the Brake Engage and the Brake Release delay times to the values listed

in

Brake Specifications for Ball Screw Linear Stage Motors

on page 89.

3. Reduce the default Stopping Time Limit from 10 seconds to 0.5 seconds,

as shown in the following display.

4. Select the Tune tab in the Axis Properties dialog box and enter the

following parameters.
a. Set the Travel Limit to no more than the travel length of the linear

stage.

b. Configure the appropriate Speed (velocity).
c. Configure the appropriate Torque/Force.

IMPORTANT

To prevent the carriage from moving, or falling when installed in a vertical
orientation, the Stopping Time Limit must be set to 0.99 seconds or less.

IMPORTANT

Check only Torque Offset, as shown below, if the linear stage is installed in a
non-horizontal mount position.