4 terminating the network – Rockwell Automation MD65 Profibus Communication Card User Manual

Page 23

Advertising
background image

Installing the PROFIBUS Module

3-7

To meet the requirements of EN55011 Class A or B, the conditions
listed below must be satisfied.

Note: For the conditions to satisfy the essential
requirements for CE compliance on MD65 drives. please
refer to the MD65 manual, D2-3519.

In applications where first environment, unrestricted
distribution is requested (EN55011 group 1, class B), the
installation requires a shielded enclosure.

3.4

Terminating the Network

The first and last node on the PROFIBUS network needs to be
terminated by using a PROFIBUS connector with terminating
resistors. See figure 3.5.

Some connector manufacturers offer standard terminating
connectors, such as the yellow ERNI PROFIBUS termination
vertical connector (Part # 103659). Standard PROFIBUS node
connectors, such as the Phoenix Subcon Plus M1 (Part #2761826),
can be configured as a terminating connector by adding resistors.

Switching

Frequency of MD65

EN55011

Class A

EN55011 Class B

4 kHz

Use one ferrite Ferrishield (part No.
HI28B2039) or Fair-Rite (part No.
0443164151)

6 kHz

No ferrite

required

8 kHz

16 kHz

Use three clip ferrites TDK, type
ZCAT 3035-1330

Figure 3.5 – Connection for Terminating Resistors

3 R x D / T x D - P

V c c 6

3 9 0 2 2 0 3 9 0 O h m

A

B

R x D / T x D - P 3

R x D / T x D - N 8

G N D 5

8 R x D / T x D - N