8-6

PROFIBUS Communications Module

8.4

Configuring the RS-485 Network

Table 8.1 shows the parameters that must be set in the daisy-
chained drives.

Note: The RS-485 network is fixed at 19.2K baud, 8 data bits, no
parity, and 1 stop bit.

Important:Parameter A105 (Comm Loss Action) in the daisy-

chained drives is still used in Multi-Drive mode. If the
RS-485 cable is disconnected or broken, the
disconnected drive(s) will immediately take the
corresponding Comm Loss Action(s). Parameter A106
(Comm Loss Time) is not used in Multi-Drive mode. On
the Profibus, Comm Flt Action (parameter 09) and Idle
Flt Action (parameter 10) in the MDCOMM-PBUS
determine the action taken for ALL of the drives on the
Multi-Drive node.

Table 8.2 shows the Multi-Drive parameters that must be set in the
MDCOMM-PBUS.

After setting the MDCOMM-PBUS parameters, set the Module
Mode Jumper from Single drive operation to Multi-Drive operation,
and reset the module or cycle power.

Table 8.1 – Parameters for daisy-chained drives

Parameter

Value

P36 (Start Source)

5 (RS485 (MDI) Port)

P38 (Speed Reference)

5 (RS485 (MDI) Port)

A103 (Comm Data Rate)

4 (“19.2K”)

A104 (Comm Node Addr)

1-247 (must be unique)

A107 (Comm Format)

0 (“RTU 8-N-1”)

Table 8.2 – Parameters for MDCOMM-PBUS

Parameter

Value

11 (MDI I/O Cfg)

0 = Drive 0 connected
1 = Drives 0-1 connected
2 = Drives 0-2 connected
3 = Drives 0-3 connected
4 = Drives 0-4 connected

17 (Drv 0 Addr)

= Parameter A104 (Comm Node Address) in Drive 0

18 (Drv 1 Addr)

= Parameter A104 (Comm Node Address) in Drive 0-1

19 (Drv 2 Addr)

= Parameter A104 (Comm Node Address) in Drive 0-2

20 (Drv 3 Addr)

= Parameter A104 (Comm Node Address) in Drive 0-3

21 (Drv 4 Addr)

= Parameter A104 (Comm Node Address) in Drive 0-4