Rockwell Automation MD65 Profibus Communication Card User Manual
Page 70

9-2
PROFIBUS Communications Module
9.1.1 DRIVE Status Indicator
Table 9.1 – DRIVE Status Indicator: State Definitions
Status
Cause
Corrective Action
Off
The module is not
powered or is not
connected properly to
the drive.
•
Securely connect the module
to the drive using the ribbon
cable.
•
Apply power to the drive.
Flashing
Red
The module is not
receiving a ping
message from the
drive.
•
Verify that cables are
securely connected.
•
Cycle power to the drive.
Solid
Red
The drive has refused
an I/O connection from
the module.
Another MDI peripheral
is using the same MDI
port as the module.
Important: Cycle power to the
product after making following
correction:
•
Verify that all MDI cables on
the MD65 drive are securely
connected and not damaged.
Replace cables if necessary.
•
Check the Events, replace
the module with a compatible
Reliance Electric branded
product (MDCOMM-PBUS).
Flashing
Green
Not Used
Solid
Green
The module is properly
connected and is
communicating with the
drive.
•
No action.
Solid
Orange
The module is booting. Wait until boot program is
complete.
Flashing
Orange
The module is in flash
mode (SW8 down).
Application Failure
•
Wait until Firmware Update
is complete, then switch
SW8 to 1.
•
Download Application code.