6 setting a fault action, 1 changing the fault action – Rockwell Automation MD65 Profibus Communication Card User Manual

Page 34

Advertising
background image

4-6

PROFIBUS Communications Module

4.6

Setting a Fault Action

By default, when communications are disrupted (for example, a
cable is disconnected) or the master is idle, the drive responds by
faulting if it is using I/O from the network. You can configure a
different response to communication disruptions using Comm Flt
Action (parameter 9) and a different response to an idle scanner
using Idle Flt Action (parameter 10).

4.6.1 Changing the Fault Action

Set the values of Comm Flt Action (parameter 9) and Idle Flt Action
(parameter 10) to the desired responses as shown in table 4.3.

!

ATTENTION: Comm Flt Action (parameter 9) and
Idle Flt Action (parameter 10) let you determine the
action of the module and connected drive if
communications are disrupted or the scanner is idle.
By default, these parameters fault the drive. You can
set these parameters so that the drive continues to
run. Precautions should be taken to ensure that the
settings of these parameters do not create a risk of
injury or equipment damage.

Table 4.3 – Selections for Drive Response to Communication Fault

Value

Action

Description

0

Fault (default)

The drive is faulted and stopped (Default).

1

Stop

The drive is stopped, but not faulted.

2

Zero Data

The drive is sent 0 for output data after a
communications disruption. This does not
command a stop.

3

Hold Last

The drive continues in its present state after a
communications disruption.

4

Send Flt Cfg

The drive is sent the data that you set in the
fault configuration parameters 13 and 14 (Flt
Cfg Logic and Flt Cfg Ref).

Figure 4.3 – Fault Action Screens on an LCD OIM

Comm Flt Action

Parameter:

#

009

Fault

0

VALUE

LIMITS

SEL

X

Idle Flt Action

Parameter:

#

010

Fault

0

VALUE

LIMITS

SEL

X

Advertising