B-4

PROFIBUS Communications Module

Sets the action that the module and the drive take if the module
detects that the scanner is idle because the controller was switched
to program mode. This setting is effective only if the I/O that controls
the drive is transmitted through the module.

Sets the configuration of the Drives that are active in the Multi-Drive
mode. Identifies the connections that would be attempted on a reset
or power cycle.

10

Idle Flt Action

Range:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Default:

0 = Fault

Type:

Read/Write

Reset Required: No

!

ATTENTION: Idle Flt Action (parameter 10) lets you
determine the action of the module and connected
drive if the scanner is idle. By default, this parameter
faults the drive. You can set this so that the drive
continues to run. Ensure that the setting of this
parameter does not create a hazard of injury or
equipment damage. Failure to observe this
precaution could result in bodily injury or damage to
equipment.

11

MDI I/O Cfg

Range:

0 = Drive 0
1 = Drives 0-1
2 = Drives 0-2
3 = Drives 0-3
4 = Drives 0-4

Default:

0

Type:

Read/Write

Reset Required: Yes