9-4

PROFIBUS Communications Module

9.1.3 NET A Status Indicator

Important:For the Multi-Daisy mode, disconnecting a MDI cable

from a daisy-chained drive does not cause an error. The
module has no indication that the drive has been
removed, except that commands to the missing drive
have no effect.

Table 9.3 – NET A Status Indicator: State Definitions

Status

Cause

Corrective Actions

Off

The module is not
powered or is not
connected properly
to the network or the
Node Address is
wrong.

Securely connect the module to
the drive using the Internal
Interface cable and to the
network using a PROFIBUS
cable. (Screw D-shell to the
module.)

Check the SW8 of DIP-
Switches and set it to one -
Normal operating state.

Check the DIP-Switches (SW1-
SW7) node address and the
Scanner setting.

Apply power to the drive.

Flashing
Red

Error in PROFIBUS
configuration.

Re-configure the PROFIBUS
module.

Solid
Red

Not Used.

Flashing
Green

Not Used.

Solid
Green

The module is
properly connected
and communicating
on the network.

No action required.