6-2

PROFIBUS Communications Module

The I/O image table will vary based on the configuration of the
Mode Jumper (J2) on the module and MDI I/O Cfg (parameter 11).
The image table always uses consecutive words starting at word 0.

Figure Figure 6.1 illustrates an example of a drive I/O image (16-bit
words).

Single drive mode is the typical configuration, where one node
consists of a MD65 drive with a MDCOMM-PBUS module.

For Multi-Drive mode, where one node can consist of up to five
drives, refer to chapter 8, Using Multi-Drive mode.

6.3

Using Logic Command/Status

When enabled, the Logic Command/Status word is always word 0 in
the I/O image. The Logic Command is a 16-bit word of control
produced by the scanner and consumed by the module. The Logic
Status
is a 16-bit word of status produced by the module and
consumed by the scanner.

This manual contains the bit definitions for compatible products
available at the time of publication in Appendix C, Logic Command/
Status Words. For other products, refer to their documentation.

Figure 6.1 – Single Drive Example of I/O Image

Controller

Scanner

Adapter

MD65 Drive

PROFIBUS

MDI

Output
Image
(Write)

Input
Image
(Read)

Message

Handler

Message

Buffer

0 Logic Status
1 Feedback

Logic Status
Feedback

Word and I/O

Message

Handler

0 Logic Command
1 Reference

Logic Command
Reference