PROFIBUS Module Parameters

B-3

No action if set to “Ready.” Resets the module if set to “Reset
Module.” Restores the module to factory default settings if set to
“Set Defaults.” This parameter is a command. It will be reset to
“0 = Ready” after the command has been performed.

Sets the action that the module and drive take if the module detects
that PROFIBUS communications have been disrupted. This setting
is effective only if I/O that controls the drive is transmitted though
the module.

8

Reset Module

Range:

0 = Ready (No action)
1 = Reset Module
2 = Set Defaults (Restores module to factory-default

settings)

Default:

0 = Ready

Type:

Read/Write

Reset Required: No

!

ATTENTION: If the module is transmitting I/O that
controls the drive, the drive may fault when you reset
the module. Determine how your drive will respond
before resetting a connected module. Failure to
observe this precaution could result in bodily injury
or damage to equipment.

9

Comm Flt Action

Range:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Default:

0 = Fault

Type:

Read/Write

Reset Required: No

!

ATTENTION: Comm Flt Action (parameter 9) and
Idle Flt Action (parameter 10) lets you determine the
action of the module and connected drive if
communications are disrupted. By default, this
parameter faults the drive. You can set this
parameter so that the drive continues to run. Take
precautions to ensure that the setting of this
parameter does not create a hazard of injury or
equipment damage. Failure to observe this
precaution could result in bodily injury or damage to
equipment.