Rockwell Automation MD65 Profibus Communication Card User Manual
Page 48

5-12
PROFIBUS Communications Module
Station 1 is configured as follows:
Note that Station 1 occupies 6 words.
Step 17. The same steps for configuring Station 1 will be used to
configure Station 2. Refer to previous steps (beginning
with step 9) for Configuring the SST-PFB-SLC PROFIBUS
Scanner Station 2. Refer to figure 5.19.
Station 2 is configured as follows:
Note that Station 2 occupies 6 words.
Step 18. Use the null modem cable that came with the scanner to
connect COM1 on the PC and the CONFIG RS232 port
on the scanner.
Important:The processor needs to be in program mode before
proceeding.
Step 19. Right-click on the scanner in the network window and
select “Connect”. Then right-click again on the scanner in
the network window and select “Load Configuration”. If a
minimum cycle time attention window pops up, click OK to
continue. After the configuration has been loaded into the
Table 5.2 – Station 1 Configurations
Module
M1/M0 Word
Ctrl/Stat & Ref Fdbk Drive 0
0
Parameter Access
2
Figure 5.19 – Station 2 Network Window
Table 5.3 – Station 2 Configurations
Module
M1/M0 Word
Ctrl/Stat & Ref Fdbk Drive 0
6
Parameter Access
8