7 viewing the module configuration – Rockwell Automation MD65 Profibus Communication Card User Manual
Page 36

4-8
PROFIBUS Communications Module
Set parameter 8 (Reset Module) to “Reset Module.” See figure 4.4.
When you enter 1 (“Reset Module”), the module will be
immediately reset. When you enter 2 (“Set Defaults”), the module
will set all module parameters to their factory-default settings. The
value of this parameter will be restored to 0 (“Ready”) after the
module is reset.
4.7
Viewing the Module Configuration
The parameters in table 4.5 provide information about how the
module is configured. You can view these parameters at any time.
Figure 4.4 – Reset Screen on an LCD OIM
Value
Description
0
Ready (Default)
1
Reset Module
2
Set Defaults
Reset Module
Parameter:
#
008
Ready
0
VALUE
LIMITS
SEL
X
Table 4.5 – Module Configuration Status Parameters
No.
Name
Description
01 Mode
Displays the Single or Multi-Drive operating mode selected
with the jumper J2 on the module.
Values
0 = Single drive operation
1 = Multi-Drive operation
04 P-DP Addr
Actual
PROFIBUS Node Address actually used by the module.
05 P-DP Rate
Actual
PROFIBUS actual operating data rate.
12 MDI I/O
Actual
Displays the Drives that are active in the Multi-Drive mode:
Bit Values
0 = Drive 0 Active
1 = Drives 0-1 Active
2 = Drives 0-2 Active
3 = Drives 0-3 Active
4 = Drives 0-4 Active