5-6
PROFIBUS Communications Module
Step 2.
Click on the (+) sign of the Slaves folder in the Library
window and the Reliance Electric sub-folder to display
the available Profibus DP slaves or the RECOMM-PBUS
slave. Refer to figure 5.6.
Step 3.
Double-click the SST-PFB-SLC MASTER in the Masters
folder in the Library window to add the scanner to the
network.
Step 4.
A user-defined Name and Description can be given to
the scanner. In our example, the scanner will be Station 0
on the network, as shown in figure 5.7.
Step 5.
Click on the Parameters tab to view the Scan Cycle
Times.
In our example, use the default settings as shown in
figure 5.8.
Figure 5.7 – SST-SST-PFB-SLC Master (General) Dialog Box
Figure 5.8 – Scan Cycle Times Dialog Box