Rockwell Automation MD65 Profibus Communication Card User Manual

Page 60

Advertising
background image

7-6

PROFIBUS Communications Module

2

IND - Index

Port ID of requested parameter

3

PVA - Parameter value

Spare

4

PVA - Parameter value (8-bit & 16-bit word).

Read Response: Contents the value from a 8-bit or 16-bit
parameter or the Fault Code (if RC = 7).

Write Response: Confirms the write value for a 8-bit or 16-
bit parameter or the Fault Code (if RC = 7).

Table 7.3 – Module Fault Code

Fault Code

Description

51

MDI Port watchdog

52

Profibus network loss

53

Not compatible product

54

MDI time-out or additional MDI master connected

Table 7.4 – Parameter Message Response Fault Numbers and Descriptions

Fault

Number

Description

101

Service not supported (i.e., set service to a read-only
parameter)

102

Service not valid

104

Parameter does not exist (i.e., parameter
number>max number of parameters)

106

Data value out of range (i.e., set value is out of range)

107

State conflict (i.e., parameter is not changeable while
the product is in an operating state)

Table 7.2 – Parameter Message Response Data

Word

Description