7-6
PROFIBUS Communications Module
2
IND - Index
Port ID of requested parameter
3
PVA - Parameter value
Spare
4
PVA - Parameter value (8-bit & 16-bit word).
Read Response: Contents the value from a 8-bit or 16-bit
parameter or the Fault Code (if RC = 7).
Write Response: Confirms the write value for a 8-bit or 16-
bit parameter or the Fault Code (if RC = 7).
Table 7.3 – Module Fault Code
Fault Code
Description
51
MDI Port watchdog
52
Profibus network loss
53
Not compatible product
54
MDI time-out or additional MDI master connected
Table 7.4 – Parameter Message Response Fault Numbers and Descriptions
Fault
Number
Description
101
Service not supported (i.e., set service to a read-only
parameter)
102
Service not valid
104
Parameter does not exist (i.e., parameter
number>max number of parameters)
106
Data value out of range (i.e., set value is out of range)
107
State conflict (i.e., parameter is not changeable while
the product is in an operating state)
Table 7.2 – Parameter Message Response Data
Word
Description