D.2.4 Drive 0-2 Control/Reference Routine

Controlling the Logic Command word in the drive. B3:22/* bits are controlled elsewhere in the user program.

0

B3:22

0

Station 2

Stop

Command

N20:4

0

Station 2

Logic Command

STOP

1

B3:22

1

Station 2

Start

Command

N20:4

1

Station 2

Logic Command

START

2

B3:22

2

Station 2

Jog

Command

N20:4

2

Station 2

Logic Command

JOG

3

B3:22

3

Station 2

Clear Faults

Command

N20:4

3

Station 2

Logic Command

CLEAR FAULTS

4

B3:22

4

Station 2

Reverse

Command

N20:4

4

Station 2

Logic Command

FORWARD

5

B3:22

4

Station 2

Reverse

Command

N20:4

5

Station 2

Logic Command

REVERSE

To control the speed reference over the Profibus, the three Reference Select bits (bits 14-12) need to have the values 011.

6

N20:4

12

Station 2

Logic Command

REFERENCE SELECT 0

7

N20:4

13

Station 2

Logic Command

REFERENCE SELECT 1

8

B3:22

5

"Never Closed"

N20:4

14

Station 2

Logic Command

REFERENCE SELECT 2

Station 2 Speed Reference

The MD65 parameter 38 - [Speed Reference]
needs to be set to 5 ("RS485 [MDI] ¨Port").
N19.5 is controlled elsewhere in the user program.

9

MOV

Move

Source

N19:5

314<

Dest

N20:5

0<

MOV

Station 2

Speed Reference

Write

10

END