4 setting the node address – Rockwell Automation MD65 Profibus Communication Card User Manual

Page 32

Advertising
background image

4-4

PROFIBUS Communications Module

4.4

Setting the Node Address

The PROFIBUS Node address/Firmware Update State is set
through the use of an 8-bit DIP switch. The low seven bits let you set
a node address and the valid address allows binary coding 1
through 125. New settings of node address are recognized only
when power is applied to the module, cycle power, or a Reset
Module Command. The MSB bit provides write access for the
module flash firmware update. In normal operating state, SW8
should be set to 1.

Refer to section 3.2, Commissioning the Module, for more
information.

Switches

1

1. The factory default states of all stitches are UP. The fault address is 3.

Description

SW1

Least Significant Bit (LSB) of Node Address

SW 2

Bit 1 of Node Address

SW 3

Bit 2 of Node Address

SW 4

Bit 3 of Node Address

SW 5

Bit 4 of Node Address

SW 6

Bit 5 of Node Address

SW 7

Most Significant Bit (MSB) of Node Address

SW 8

SW8 Firmware Update

Figure 4.2 – Setting the Node Address

SW 8 Setting

Description

0

Write Access Firmware Update

1

Normal Operating State

J2

J2

Single Drive

Operation

Multi-Drive

Operation

2

1

8

3 4 5

6 7

NODE
ADDRESS SWITCHES

UP = OPEN = 1

2

1

8

3 4 5

6 7

J3

SWAP

J4

J1