2 module diagnostic items in single drive mode, 3 module diagnostic items in multi- drive mode – Rockwell Automation MD65 Profibus Communication Card User Manual

Page 73

Advertising
background image

Troubleshooting the PROFIBUS Module and Network

9-5

9.2

Module Diagnostic Items in Single
Drive Mode

Table 9.4 lists diagnostic items that can be accessed using
V*S Utilities software or the LCD OIM.

9.3

Module Diagnostic Items in Multi-
Drive Mode

For the Multi-Drive mode it is not possible to connect a peripheral
device such as an OIM or MDCOMM-232 (V*S Utilities). Table 9.5
lists diagnostic items that can only be accessed via Profibus
network in Multi-Drive mode.

Table 9.4 – Module Diagnostic Items for Single Drive Mode

No.

Event

Description

1

Field Flash Cnt

The number of Firmware Updates.

2

Module Events

The number of events in the event queue.

3

Reference

Reference from PROFIBUS returned to MDI drive.

4

Logic Cmd

Command from PROFIBUS returned to MDI drive.

5

Logic Sts

Status of the drive returned to PROFIBUS.

6

Feedback

Feedback from drive returned to PROFIBUS.

7

PROFIBUS Rx
Errors

Current value of the PROFIBUS Receive Error
Counter register.

8

PROFIBUS Tx
Errors

Current value of the PROFIBUS Transmit Error
Counter register.

9

Data Rate

Current setting of the PROFIBUS baud rate.

10

Node Address

Current setting of the module Node address switch.

Table 9.5 – Module Diagnostic Items for Multi-Drive Mode

No.

Event

Description

1

Field Flash Cnt

The number of Firmware Updates.

2

Module Events

The number of events in the event queue.

3

Drv 0 Reference Reference from Profibus returned to MDI Drive 0.

4

Drv 0 Logic Cmd Command from Profibus returned to MDI Drive 0.

5

Drv 0 Logic Sts

Status of the Drive 0 returned to Profibus.

6

Drv 0 Feedback Feedback from Drive 0 returned to Profibus

7

Drv 1 Reference Reference from Profibus returned to MDI Drives 0-1.

8

Drv 1 Logic Cmd Command from Profibus returned to MDI Drive s0-1.

9

Drv 1 Logic Sts

Status of the Drives 0-1 returned to Profibus.

Advertising