D.2.5 parameter accessing routine, D-11, Slc ladder logic examples – Rockwell Automation MD65 Profibus Communication Card User Manual

Page 97

Advertising
background image

SLC Ladder Logic Examples

D-11

D.2.5 Parameter Accessing Routine

r

This section of the outine is only needed if the application needs to perform Parameter Protocol Reads or Writes to Station 2.

On power-up, initialize the Parameter Protocol routine.

0

S:1

15

First Pass

U

B3:19

0

Par Prot

Messaging

Request

This circuit utilizes the Para meter Protocol. A REQUEST to the Profibus adapter is processed only one at a time,

and after each RESPONSE from the adapter a zero must be sent and received to 'handshake' before the next

REQUEST/RESPONSE transaction can take place. For example:

Send a parameter read request --> Receive a parameter read response --> Send a "0" --> Receive a "0" --> [Transaction complete]

If the RESPONSE PCA Word 1 (N10:6) is "0", then a REQUEST can be initiated

.

Elsewhere in the user program these words must be loaded with message data prior to initiating the REQUEST.

N7:10 = RC = the operation to be performed ("1" = Read, "2" = 16-bit Write)

N7:11 = PNU = the parameter number to read or write

N7:12 = Subindex = the MDIport # ("0" = Station 0, "1" = Station 1, "2" = Station 2, "5" = MDCOMM-PBUS, etc.)

N7:13 = PVA #1 (the parameter value (high word)) - only used when writing parameters

N7:14 = PVA #2 (the parameter value (low word)) - only used when writing parameters

The four Parameter Protocol Words set up in the scanner are used to perform the Parameter Protocol:

N20:6 = contains RC (the operation to be performed) and PNU (the parameter number to read or write) combined

N20:7 = Subindex (the MDIport #)

N20:8 = PVA #1 (the parameter value (high word))

N20:9 = PVA #2 (the parameter value (low word))

B3:19/0 is turned ON elsewhere in the program after a REQUEST message (N7:10-14) is loaded. This causes one

Parameter Protocol read or write to occur and B3:19/0 is turned OFF when the transaction is complete.

1

B3:19

0

Par Prot

Messaging

Request

EQU

Equa

Source A

N10:6

0<

Source B

0

0<

EQU

RESPONSE

PCA Word

MOV

Move

Source

N7:11

77<

Dest

N20:6

12304<

MOV

PCA Word

N7:10

0

RC bit 0

L

N20:6

12

PCA Word

RC bit 0

N7:10

1

RC bit 1

L

N20:6

13

PCA Word

RC bit 1

N7:10

2

RC bit 2

L

N20:6

14

PCA Word

RC bit 2

COP

Copy File

Source

#N7:12

Dest

#N20:7

Length

3

COP

IND Word

(Subindex)

N10:6 is the Response Parameter Access Word 1. It is <> 0 when a message has been received in response to a

message request. If the response is >= 7000 hex (28672 decimal), then the adapter is responding that an error has occurred.

In this case, the returned data in the response will contain a fault code and not the parameter value data.

The response message can be found at:

N7:20 = PCA Word = contains RC and PNU

N7:21 = Subindex = the MDIport # ("0" = Station 0, "1" = Station 1, "2" = Station 2, "5" = MDCOMM-PBU

S, etc.)

N7:22 = PVA #1 = the parameter value (high word)

N7:23 = PVA #2 = the parameter value (low word)

The PVA's will either contain parameter read data, echo the parameter write data or contain an error code if unsuccessful.

2

B3:19

0

Par Prot

Messaging

Request

NEQ

Not Equal

Source A

N10:6

0<

Source B

0

0<

NEQ

RESPONSE

PCA Word

COP

Copy File

Source

#N10:6

Dest

#N7:20

Length

4

COP

RESPONSE Message

PCA Word

MOV

Move

Source

0

0<

Dest

N20:6

12304<

MOV

PCA Word

U

B3:19

0

Par Prot

Messaging

Request

3

END