Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual

Page 141

Advertising
background image

Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

141

FactoryTalk EnergyMetrix Software Meter and Tag Setup Chapter 7

10.

Confirm the meter was created in the correct
group.

11.

Repeat steps 1…10 to create the rest of the energy meters that are assigned to PowerMonitor status inputs.

For this example, enter the data in the table for the Air Flow and Water Main meters. Make sure to create each meter
under the correct parent group.

For the

Efficient Industries Plant 1

example,

the meter listing should look like this.

Meter

Parent Group

Meter Type

Device

Name

Air Flow

Air

Air

Production 2

Air Flow Meter

Water Main

Water

Water

MCC 2

Water Main Meter