FactoryTalk View ME Energy Faceplates

14. Click the Communication tab on

the Message Configuration dialog
box.
a. Click the Browse icon.
b. Select the path to the

PowerMonitor device.

For this example, select ETHERNET-MODULE MCC2_PM1000.

c. Click OK, then verify the path is correct.
d. Verify CIP is the Communication Method.
e. Click OK to close the Message Configuration dialog box.

15. Assign the Val_Status_Input parameter to the

associated controller-scoped tag.
a. Double-click the tag name field next to

Val_Status_Input parameter.

b. Click the pull-down menu icon then double-click

the associated controller-scoped tag to select it.

For this example, the tag is MCC_2_Status1Count.

16. Assign energy input calculation and alarm setpoints based on the

Energy Add-On Instruction Factor table definitions on

page 329

.

One table provides factor definitions for electric inputs and one
for all other energy inputs.

This example shows values that need to be set for the
Energy_Gas_PM_Status Add-On Instruction.