Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

265

FactoryTalk View ME Energy Faceplates

Chapter 11

Configure ME E3PLUS Faceplates

The ME E3PLUS Faceplate files provide a pre-configured display and associated logic for the E3 Plus Solid State Overload
Relay using FactoryTalk View Machine Edition and RSLogix 5000. The faceplate includes status, control, diagnostic, and
energy views controlled by its own toolbar buttons.

The E3 Plus faceplate is compatible only with the E3 Plus Overload Relays communicating with the 193-DNENCAT.

DeviceNet to EtherNet/IP Network Setup

In order for the faceplate add-on instruction to function properly in your RSlogix5000 application, you need to configure
the following parameters for your E3 Plus module:

• Param 59, Output Assembly = 105
• Param 60, Input Assembly = 100
• Param 61, Assy Word 0 Param = 21 (supplies status of Inputs and Outputs)
• Param 62, Assy Word 1 Param = 4 (supplies Avg current)
• Param 63, Assy Word 2 Param = 14 (supplies Trip Status)
• Param 64, Assy Word 3 Param = 15 (supplies Warning Status)

Shows status and provides operator control of
the Trip Reset and Outputs A and B.

Shows the last fault.

Home Display

Fault Display

Configuration Display

Energy Display

Lets you rename the device for display at the
top of the faceplate.

Shows basic energy data.