Map energy add-on instruction, Tags to plc-5 addresses – Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual
Page 86

86
Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
Chapter 3 Energy Data Collector Configuration
Map Energy Add-On Instruction Tags to PLC-5 Addresses
After programming the CompactLogix energy Add-On Instructions, you must map the total energy tags
(
AOIName.Val_Total_xxx) to PLC-5 type addresses (Fxx:x) that FactoryTalk EnergyMetrix software can read. You will
create a MOV instruction for each Compactlogix energy Add-On Instruction to move its total to a tag within an array
named
ControllerName_EnergyTotals. You will then map that array to the PLC-5 file F10.
Refer to the CompactLogix tab of the Energy Data Worksheet for the CompactLogix EnergyTotal and PLC-5 tags that
must be mapped.
The worksheet below shows the tags to be mapped for the Efficient Industries Plant 1 example.
Follow these steps to map the total energy Add-On Instruction tags to PLC-5 type addresses.
1.
Open your program routine and
create a new rung.
For this example, a new rung is
added after
the Energy Add-On Instruction
rung.
TIP
Tag mapping must be done in Offline mode.