Chapter 11
FactoryTalk View ME Energy Faceplates
e. Click the Communication tab.
f. Add the 193-DNENCAT port number and your E3 Plus node address to your path configuration in the
following format: Motor1, 3, #.
Import Program Control Rungs
Example logic is provided for configuring program commands. Follow these steps to import this configuration.
1. Choose a routine for importing the new rungs.
2. On a new rung, right click and select 'Import Rungs…'
3. From the ME E3 Plus Faceplate Files folder, select "E3Plus_Control_Rungs.L5X." Click Import.
4. Click Tags within the Import Content organizer.
5. Replace "_DeviceName" in the Final Name field with the name of your E3 Plus device. Click OK.
TIP
Motor_1 - the name of the EtherNet/IP Communications Auxiliary
3 - the port number of the DeviceNet Scanner of the EtherNet/IP Communications Auxiliary.
5 - the node address of the E3 Plus Overload Relay.